Designing a Class 9c Aged Care Building: Three Early Fire Safety Decisions That Shape the Layout

A Class 9c building is, in NCC terms, one for the residential accommodation of aged persons who, due to varying degrees of incapacity associated with ageing, are provided with personal care services and 24 hour staff assistance. Residents are assisted to evacuate in an emergency, so the fire safety approach is different to ordinary apartments. Three decisions made early tend to shape the whole floor plan.

The provisions below are drawn from NCC 2022. Check the edition that applies to your approval, including NCC 2025 once it becomes mandatory in the ACT, and confirm against the current text.

1. Compartmentation

NCC 2022 Part C3 requires smoke-proof walls to divide a Class 9c building into areas of no more than 500 m². Fire compartments are separated by fire walls, with floors rated at FRL 60/60/60, and doorways in fire walls need –/60/30 doors. Kitchens over 30 m², laundries with potential fire-source equipment and records storage over 10 m² must be separated from sole-occupancy units by smoke-proof walls. Compartment boundaries drive wing layouts, corridor lengths and where staff stations can sit, so test them against the concept plan early.

2. Sprinklers

Specification 17 sets out sprinkler requirements for Class 2, 3 and 9c buildings. For buildings of up to four storeys the system follows AS 2118.4, and taller buildings follow AS 2118.1. It also requires a monitored main stop valve and a permanent link to the fire station or dispatch centre. Coordinate plant space, water supply and ceiling services with the hydraulic and fire engineers before layouts are locked.

3. Detection and smoke hazard management

Part E2 requires automatic smoke warning in sleeping areas of Class 9c buildings. Up to 25 m effective height, a detection and alarm system to Specification 20 is required throughout, with detection to AS 1670.1. Above two storeys, pressurised fire-isolated exits or open access ramps or balconies are required.

When a Performance Solution helps

Contemporary aged care models such as home-like clusters with open living areas often sit awkwardly against deemed-to-satisfy compartment limits. A fire engineered Performance Solution can resolve this, but it needs to start at concept stage and be agreed with the certifier and fire brigade early.

Our BCA consultancy team reviews aged care concepts against the NCC before sketch plans are fixed, so that the compartment, sprinkler and detection strategy supports the design rather than fighting it.